GE IS200TSVOH1BCC Rack mounted Power Board
stars, based on 0reviews
IS200TSVOH1BCC Product Description
24VDC positive logic electronic short circuit protection
output module
gfk - 1288 b
Discrete output module
June 1997
Limit current at each point
The following figure shows the current limitations of surge circulation and steady state
Conditions.
Built in overcurrent protection tripping, if the specified value or duration of the current
If the steady-state current is specified. Short circuit protection tripping
Load is short selling. The automatic 1.5ms retry function helps to trip from incorrect circuits
Noise. Once overcurrent or short circuit is detected, the retry circuit will shut down that point
And return within 1.5 milliseconds. If the problem persists, the module is experiencing a circuit malfunction. of
The module then closes the point regardless of its command status. Two LED lights are on
An error occurred. When a fault occurs, the state of that point cannot be changed, that is, the fault
Clear it in order to open the point. Method to clear errors
Appropriate datagrams or clearing fault tables or cycling user power. steady state
The overcurrent protection is set to trip at approximately 2.5 amperes. This protects the module
Overcurrent, i.e. non tripping short circuit protection.
careful
The steady-state current is limited to 2 amperes per point and 8 amperes per module.
Not following these load guidelines may result in misoperation or
Destruction of modules.
stable state
7535 6
Surge and steady-state rated values
Time (Madam)
current
(Ampere) 46746
External power requirements
The external power supply used in conjunction with the module provides on-site power to the module
The module is in a short circuit period.
When the load is short circuited, insufficient external power supply may lead to a decrease in electric field power
Below the specified working range, resulting in module misoperation. external
The power supply can provide non degraded short-circuit energy
Output voltage level. The amount of energy required depends on the quantity
Possible short-term points that may occur simultaneously. Reference power short circuit
Before selecting a power supply to be used with the module, follow the operating procedures.
Local energy storage (batteries or capacitors) can be used to compensate
Insufficient power characteristics.
Important reminder: Additional practices include reducing wiring resistance from
External power supply of module, voltage drops when short circuiting energy
Transfer.
24VDC positive logic electronic short circuit protection
output module
gfk - 1288 b
4 Discrete Output Modules
June 1997
Module specifications
Module Features
User input voltage 18-3VDC, nominal 24VDC
Output voltage range 17.5 VDC to 29.5 VDC
Continuous load current of 2 amperes per point
Each module has an additional 8 amperes
Each module outputs 8
Single item score status (green)
Single fault status (yellow) On=Fault
BIU5V status and external power supply (green)
From user terminal to logic,
From the user terminal to the frame ground,
Group, group
25VAC continuous, 15VAC for 1 minute.
There is no connection between the points in a group.
Current drawn from bus interface
Unit power supply
125mAh
output characteristic
The duration of a surge of 1 ampere per point is 1mS
Steady state overcurrent trip
drop
Nominal range 2.25 amperes -2.75 amperes
Output voltage drops by 5 volts
Output leakage current. 5mA, 3VDC
Response time is 5 µ
Response to compensatory leave of 5 µ
Short circuit response time 2 amperes 1 µ s
The retry interval is 1.5 milliseconds longer
Short circuit protection, overcurrent protection, MOV protection